OLPD Testing and Fault Location on 33 kV Offshore Wind Turbine Subsea Cables from an Oil Platform
OLPD Testing and Fault Location on 33 kV Offshore Wind Turbine Subsea Cables from an Oil Platform 33 kV Cable Feeder Oil & Wind Industries HFCT Sensors Cable Mapping Solution Tests OLPD Test 1 was carried out at the 33 kV gas insulated switchboard (GIS) at the main production platform using the HVPD LongshotTM test unit with a combination of HFCT and TEV sensors attached to each phase of the cable at the earthed terminations. This first test measured the PD up to and including the 33 kV ring main unit (RMU) located at the bottom of the Turbine A Tower, 1240 m away. OLPD Test 2 was then carried out at the RMU at Turbine A to pinpoint the location of the PD source that was detected in OLPD Test 1, using TDR pulse timing measurement techniques as described below. Project OLPD Test 1 was carri