Design of a bored pile retaining wall using 600mm diameter bored concrete piles 12.5m long, installed with a restricted access mini piling rig.

Design of a bored pile retaining wall using 600mm diameter bored concrete piles 12.5m long, installed with a restricted access mini piling rig.

London & Midlands 0207 206 2576 01788 211778 North & Scotland 01423 589500 admin@RemedyGeotechnics.com Leave the ground to us! www.remedygeotechnics.com Follow Us @RemGeotechnics CASE STUDY A burst water main led to collapsed dry stone retaining wall, impairing traffic flows along the B6143. Support for the repaired road was urgently needed, complicated by special constraints and tight timescales. Design of a bored pile retaining wall using 600mm diameter bored concrete piles 12.5m long, installed with a restricted access mini piling rig. Remedy were called in to develop a permanent retaining solution to support the B6143, Oakworth Road into Keighley. An existing 5m high, dry stone retaining wall had collapsed as the result of a bur