Case Study
Birdsboro - Pine Lane 69kV
Birdsboro Pine Lane 69kV Birdsboro Pine Lane 69kV Double Circuit Wood Pole Rebuild North Boyertown, PA Based on the expected 2013 summer peak load conditions, an outage at North Boyertown 230/69kV transformer No.1, with Panther Creek Generator out of service, resulted in a flow on the Birdsboro Pine Lane 69kV line that exceeded 106% of its emergency rating. The normal/emergency rating of the 69kV line is 55/56 MVA (SN/SE). A majority of the