Retrofit Existing Burner To Meet Low Nox Emissions Requirements

Retrofit Existing Burner To Meet Low Nox Emissions Requirements

Pages 2 Pages

BOILER DIVISION CASE STUDY Mission Hospital Mission Viejo, California Burner Retrofit CUSTOMER APPLICATION AND KEY CHALLENGES In response to overcrowding and con- sistently operating at or above capac- ity levels, Mission Hospital recently approached R.F. MacDonald Co. after embarking on construction of a four- story, 94,730 square foot facility that would offer an additional 64 private patient beds, as well as become the new home for trauma services, the surgi- cal intensive care unit, neuroscience center, diagnostic imaging and hospital chapel. At the time, the hospital was running off of two Kewanee 250HP H35- 250-G Boilers which are responsible for heating, hot water, humidification, and sterilization in the current tower. One of the current units was operating at 30ppm N