Pro Moss , Scale Prevention, and Water Savings

Pro Moss , Scale Prevention, and Water Savings

© 2016 Creative Water Solutions Providing naturally pure, healthier water. Moss Briefs: ProMoss TM , Scale Prevention, and Water Savings What: Mammoth cooling tower, 500 tons, 1675 gallon sump, averaging 7800 gpd makeup water Installed: April 2016 at an office building in Minneapolis, MN Treatment: ProMossTM with CWT-595 inhibitor being fed at less than 50% of its normal dosage rate Cycles of Concentration: 8.5 – where 5 is normal, decreasing bleed by 47% and resulting in 10% overall water savings Chemistry example: - Total hardness: 908 ppm - TDS: 1880 - PTSA: 89 ppm - P Alkalinity: 90 ppm - M Alkalinity: 520 ppm - pH 9.3 Biology: Weekly bacteria dip slides have not exceeded 10 4 all season, regularly below 10 3 “I continue to be impressed by the