Case Study Solihull Hospital Solihull Hospital This 350-bed hospital is a smaller site with newer buildings than Birmingham Heartlands. As was the case with Heartlands, a temperature regime was applied as the sole Legionella control measure. This proved difficult to maintain. Mixing valves had to be fitted and rubber lined flexible hoses and rubber fittings were attached to several outlets. Water stagnation was also possible due to poor use of outlets and ward closures - ideal conditions for Legionella proliferation. Following the success of Orca at Heartlands, one copper and silver ionization system, with eight copper and four silver electrode chambers, was installed in January 2008. Prior to installation 30 outlets were sampled, of which seven tested positive (23%). Coun